Troubleshooting exercise

Chapter 5: Load take over (LTO) - 1460 P>2


You are correct, 1460 P>2 is tripping the breaker.

Disable the protection and you should be able to set the correct operational sequence.


As you saw the overload alarm is set to 5%, that can be confusing, the 5% is an expression of if the load on the genset is above 5%.

So this means that if the alarm should be used as an overload alarm, the correct value should be 105%